Project name
The Solar Plant Earthing Design Calculator worked example uses Project name = Solar PV Plant. This value is passed directly into the calculation.
Plant capacity
The Solar Plant Earthing Design Calculator worked example uses Plant capacity = 6 MW AC. This value is passed directly into the calculation, with an allowed minimum 0.
DC capacity
The Solar Plant Earthing Design Calculator worked example uses DC capacity = 7.5 MWp. This value is passed directly into the calculation, with an allowed minimum 0.
Plant type
The Solar Plant Earthing Design Calculator worked example selects “Ground-mounted”. Available choices include Ground-mounted, Rooftop / large commercial, and Hybrid / other. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
System type
The Solar Plant Earthing Design Calculator worked example selects “MV (1–36 kV)”. Available choices include LV (≤ 1 kV), MV (1–36 kV), and HV (> 36 kV). This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Evacuation / system voltage
The Solar Plant Earthing Design Calculator worked example uses Evacuation / system voltage = 33 kV. This value is passed directly into the calculation, with an allowed minimum 0.4.
System frequency
The Solar Plant Earthing Design Calculator worked example uses System frequency = 50 Hz. This value is passed directly into the calculation, with an allowed minimum 40 and maximum 70.
Number of inverter stations
The Solar Plant Earthing Design Calculator worked example uses Number of inverter stations = 4. This value is passed directly into the calculation, with an allowed minimum 0.
Number of transformers
The Solar Plant Earthing Design Calculator worked example uses Number of transformers = 2. This value is passed directly into the calculation, with an allowed minimum 0.
Number of MV panels / switchgear sections
The Solar Plant Earthing Design Calculator worked example uses Number of MV panels / switchgear sections = 3. This value is passed directly into the calculation, with an allowed minimum 0.
Soil model
The Solar Plant Earthing Design Calculator worked example selects “Uniform soil”. Available choices include Uniform soil, Two-layer soil, and Multilayer soil. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Soil resistivity ρ (design value)
The Solar Plant Earthing Design Calculator worked example uses Soil resistivity ρ (design value) = 10 Ω·m. This value is passed directly into the calculation, with an allowed minimum 0.1. Measured value used for the grid calculation. Must be greater than zero.
Surface-layer resistivity ρs
The Solar Plant Earthing Design Calculator worked example uses Surface-layer resistivity ρs = 3000 Ω·m. This value is passed directly into the calculation, with an allowed minimum 0. Crushed rock / gravel surfacing. Enter 0 only if there is genuinely no surface layer.
Surface-layer thickness hs
The Solar Plant Earthing Design Calculator worked example uses Surface-layer thickness hs = 0.1 m. This value is passed directly into the calculation, with an allowed minimum 0 and maximum 1.
Grid burial depth h
The Solar Plant Earthing Design Calculator worked example uses Grid burial depth h = 0.6 m. This value is passed directly into the calculation, with an allowed minimum 0.1 and maximum 3.
Seasonal / dry-condition resistivity
The Solar Plant Earthing Design Calculator worked example uses Seasonal / dry-condition resistivity = 0 Ω·m. This value is passed directly into the calculation, with an allowed minimum 0. Optional. If entered and higher than ρ, the design is also screened against it.
Soil-test reference
The Solar Plant Earthing Design Calculator worked example selects “Wenner 4-pin test”. Available choices include Wenner 4-pin test, Schlumberger test, and Assumed / not yet measured. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
System fault current If
The Solar Plant Earthing Design Calculator worked example uses System fault current If = 25 kA. This value is passed directly into the calculation, with an allowed minimum 0.01.
Maximum earth-fault current
The Solar Plant Earthing Design Calculator worked example uses Maximum earth-fault current = 25 kA. This value is passed directly into the calculation, with an allowed minimum 0.01. Used for conductor thermal sizing when higher than the split grid current.
Fault type
The Solar Plant Earthing Design Calculator worked example selects “Single line-to-ground”. Available choices include Single line-to-ground, Double line-to-ground, and Other / as per system study. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Fault duration tc (thermal)
The Solar Plant Earthing Design Calculator worked example uses Fault duration tc (thermal) = 1 s. This value is passed directly into the calculation, with an allowed minimum 0.05 and maximum 10.
Shock duration ts (safety)
The Solar Plant Earthing Design Calculator worked example uses Shock duration ts (safety) = 0.5 s. This value is passed directly into the calculation, with an allowed minimum 0.05 and maximum 3. Body shock duration used for tolerable touch and step voltage. Often shorter than tc.
Breaker interruption time
The Solar Plant Earthing Design Calculator worked example uses Breaker interruption time = 0.06 s. This value is passed directly into the calculation, with an allowed minimum 0.
Protection relay operating time
The Solar Plant Earthing Design Calculator worked example uses Protection relay operating time = 0.3 s. This value is passed directly into the calculation, with an allowed minimum 0.
Fault-current division factor Sf
The Solar Plant Earthing Design Calculator worked example uses Fault-current division factor Sf = 0.7. This value is passed directly into the calculation, with an allowed minimum 0.01 and maximum 1. Portion of the fault current returning through the earth grid. IG = If × Sf.
Decrement factor Df
The Solar Plant Earthing Design Calculator worked example uses Decrement factor Df = 1. This value is passed directly into the calculation, with an allowed minimum 1 and maximum 1.6. Asymmetry allowance. 1.0 disables it.
X/R ratio
The Solar Plant Earthing Design Calculator worked example uses X/R ratio = 10. This value is passed directly into the calculation, with an allowed minimum 0.
Future fault-current margin
The Solar Plant Earthing Design Calculator worked example uses Future fault-current margin = 0 %. This value is passed directly into the calculation, with an allowed minimum 0 and maximum 100.
Grid length Lx
The Solar Plant Earthing Design Calculator worked example uses Grid length Lx = 70 m. This value is passed directly into the calculation, with an allowed minimum 1.
Grid width Ly
The Solar Plant Earthing Design Calculator worked example uses Grid width Ly = 50 m. This value is passed directly into the calculation, with an allowed minimum 1.
Grid conductor spacing D
The Solar Plant Earthing Design Calculator worked example uses Grid conductor spacing D = 5 m. This value is passed directly into the calculation, with an allowed minimum 0.5 and maximum 40.
Additional interconnection conductor length
The Solar Plant Earthing Design Calculator worked example uses Additional interconnection conductor length = 0 m. This value is passed directly into the calculation, with an allowed minimum 0.
Peripheral conductor included
The Solar Plant Earthing Design Calculator worked example selects “Yes — closed peripheral loop”. Available choices include Yes — closed peripheral loop and No. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Internal mesh included
The Solar Plant Earthing Design Calculator worked example selects “Yes — internal mesh conductors”. Available choices include Yes — internal mesh conductors and No. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Array field length
The Solar Plant Earthing Design Calculator worked example uses Array field length = 300 m. This value is passed directly into the calculation, with an allowed minimum 0.
Array field width
The Solar Plant Earthing Design Calculator worked example uses Array field width = 200 m. This value is passed directly into the calculation, with an allowed minimum 0.
Number of MMS / table blocks
The Solar Plant Earthing Design Calculator worked example uses Number of MMS / table blocks = 60. This value is passed directly into the calculation, with an allowed minimum 0.
Bonding conductor per MMS block
The Solar Plant Earthing Design Calculator worked example uses Bonding conductor per MMS block = 12 m. This value is passed directly into the calculation, with an allowed minimum 0. Average run to bond one table row into the array grid.
Maximum spacing between earth connections
The Solar Plant Earthing Design Calculator worked example uses Maximum spacing between earth connections = 30 m. This value is passed directly into the calculation, with an allowed minimum 2. Project design criterion — not an IEEE 80 equation.
Array perimeter grid material
The Solar Plant Earthing Design Calculator worked example selects “GI flat”. Available choices include GI flat, Copper flat, and Aluminium flat. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Array perimeter grid depth
The Solar Plant Earthing Design Calculator worked example uses Array perimeter grid depth = 0.6 m. This value is passed directly into the calculation, with an allowed minimum 0.1 and maximum 3.
Electrode type
The Solar Plant Earthing Design Calculator worked example selects “GI pipe electrode”. Available choices include GI pipe electrode, GI rod electrode, Copper / copper-bonded rod, and Chemical earth electrode. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Electrode diameter
The Solar Plant Earthing Design Calculator worked example uses Electrode diameter = 40 mm. This value is passed directly into the calculation, with an allowed minimum 5.
Electrode length
The Solar Plant Earthing Design Calculator worked example uses Electrode length = 3 m. This value is passed directly into the calculation, with an allowed minimum 0.5.
Electrode / rod quantity in the grid
The Solar Plant Earthing Design Calculator worked example uses Electrode / rod quantity in the grid = 12. This value is passed directly into the calculation, with an allowed minimum 0.
Electrode spacing
The Solar Plant Earthing Design Calculator worked example uses Electrode spacing = 6 m. This value is passed directly into the calculation, with an allowed minimum 0.5.
Soil enhancement treatment
The Solar Plant Earthing Design Calculator worked example selects “None — natural backfill”. Available choices include None — natural backfill, Bentonite backfill, and Chemical earthing compound. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Main grid conductor material
The Solar Plant Earthing Design Calculator worked example selects “GI / zinc-coated steel”. Available choices include GI / zinc-coated steel, Copper, Aluminium, and Steel (bare). This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Conductor sizing method
The Solar Plant Earthing Design Calculator worked example selects “IEEE 80 thermal equation (eq. 37)”. Available choices include IEEE 80 thermal equation (eq. 37) and IS 3043 / CBIP k-factor: A = I√t / k. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Initial / ambient conductor temperature
The Solar Plant Earthing Design Calculator worked example uses Initial / ambient conductor temperature = 40 °C. This value is passed directly into the calculation, with an allowed minimum -10 and maximum 90.
Maximum allowable conductor temperature
The Solar Plant Earthing Design Calculator worked example uses Maximum allowable conductor temperature = 0 °C. This value is passed directly into the calculation, with an allowed minimum 0. Leave 0 to use the IEEE 80 material fusing / limit temperature.
Design margin on conductor area
The Solar Plant Earthing Design Calculator worked example uses Design margin on conductor area = 30 %. This value is passed directly into the calculation, with an allowed minimum 0 and maximum 100.
Main grid conductor size
The Solar Plant Earthing Design Calculator worked example selects “Auto — smallest standard size that passes”. Available choices include Auto — smallest standard size that passes, 25 × 3 mm (75 mm²), 25 × 6 mm (150 mm²), 32 × 6 mm (192 mm²), and 40 × 6 mm (240 mm²). This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Transformer rating
The Solar Plant Earthing Design Calculator worked example uses Transformer rating = 6.5 MVA. This value is passed directly into the calculation, with an allowed minimum 0.
Transformer earth-fault current
The Solar Plant Earthing Design Calculator worked example uses Transformer earth-fault current = 25 kA. This value is passed directly into the calculation, with an allowed minimum 0.01.
Transformer fault duration
The Solar Plant Earthing Design Calculator worked example uses Transformer fault duration = 1 s. This value is passed directly into the calculation, with an allowed minimum 0.05 and maximum 10.
Transformer body earthing material
The Solar Plant Earthing Design Calculator worked example selects “GI flat”. Available choices include GI flat and Copper flat. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Transformer body conductor size
The Solar Plant Earthing Design Calculator worked example selects “Auto — smallest standard size that passes”. Available choices include Auto — smallest standard size that passes, 25 × 3 mm (75 mm²), 25 × 6 mm (150 mm²), 32 × 6 mm (192 mm²), and 40 × 6 mm (240 mm²). This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Transformer neutral earthing material
The Solar Plant Earthing Design Calculator worked example selects “Copper flat”. Available choices include Copper flat and GI flat. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Transformer neutral conductor size
The Solar Plant Earthing Design Calculator worked example selects “Auto — smallest standard size that passes”. Available choices include Auto — smallest standard size that passes, 25 × 3 mm (75 mm²), 25 × 6 mm (150 mm²), 32 × 6 mm (192 mm²), and 40 × 6 mm (240 mm²). This selection may change the method or factor used by the engine, so choose the option that matches the real case.
Body earth connections per transformer
The Solar Plant Earthing Design Calculator worked example uses Body earth connections per transformer = 2. This value is passed directly into the calculation, with an allowed minimum 0.
Neutral earth connections per transformer
The Solar Plant Earthing Design Calculator worked example uses Neutral earth connections per transformer = 2. This value is passed directly into the calculation, with an allowed minimum 0.
Transformer-to-grid connection length
The Solar Plant Earthing Design Calculator worked example uses Transformer-to-grid connection length = 10 m. This value is passed directly into the calculation, with an allowed minimum 0.
RMU / VCB units
The Solar Plant Earthing Design Calculator worked example uses RMU / VCB units = 2. This value is passed directly into the calculation, with an allowed minimum 0.
Lightning arrester sets
The Solar Plant Earthing Design Calculator worked example uses Lightning arrester sets = 3. This value is passed directly into the calculation, with an allowed minimum 0.
CT / PT units
The Solar Plant Earthing Design Calculator worked example uses CT / PT units = 6. This value is passed directly into the calculation, with an allowed minimum 0.
Cable tray run length
The Solar Plant Earthing Design Calculator worked example uses Cable tray run length = 400 m. This value is passed directly into the calculation, with an allowed minimum 0.
Boundary fence length
The Solar Plant Earthing Design Calculator worked example uses Boundary fence length = 1000 m. This value is passed directly into the calculation, with an allowed minimum 0.
Number of gates
The Solar Plant Earthing Design Calculator worked example uses Number of gates = 2. This value is passed directly into the calculation, with an allowed minimum 0.
Maximum fence earth-connection spacing
The Solar Plant Earthing Design Calculator worked example uses Maximum fence earth-connection spacing = 50 m. This value is passed directly into the calculation, with an allowed minimum 5.
Project grid-resistance criterion
The Solar Plant Earthing Design Calculator worked example uses Project grid-resistance criterion = 1 Ω. This value is passed directly into the calculation, with an allowed minimum 0.01. Project / AHJ criterion only. It is never used on its own to declare the design safe.
Body weight assumption
The Solar Plant Earthing Design Calculator worked example uses Body weight assumption = 50 kg. This value is passed directly into the calculation, with an allowed minimum 50 and maximum 70. IEEE 80 tolerable-voltage body criterion: 50 kg (0.116) or 70 kg (0.157).
Auto-optimise earthing design
The Solar Plant Earthing Design Calculator worked example selects “No — evaluate my configuration as entered”. Available choices include No — evaluate my configuration as entered and Yes — tighten spacing / add rods until the safety checks pass. This selection may change the method or factor used by the engine, so choose the option that matches the real case.