AC Cable Sizing Calculator

Size the AC cable from a solar inverter to the distribution board, sized on inverter output current with a 1% voltage-drop target.

Inputs

Grid inverters normally run at unity

Formula

  • I_ac = P / (V × pf) for 1-ph or P / (√3 × V × pf) for 3-ph
  • Protective device I_n ≥ 1.25 × I_ac
  • A_min = k × ρ × L × I / (limit% × V)

The inverter AC cable is a continuous-duty circuit, so IEC practice applies a 1.25 continuous-load factor to the protective device and requires the cable to carry the full inverter rated output indefinitely. Because inverters trip on grid over-voltage, keeping the AC-side drop at or below 1% also prevents nuisance disconnection on sunny days when the point of connection is already near the upper voltage limit.

Step-by-step calculation

  1. AC current

    P / (√3 V pf)

    13.912 A

  2. Continuous rating

    1.25 × I

    17.39 A

  3. Area for voltage drop

    √3 ρ L I / (limit × V)

    2.5 mm²

  4. Selected

    max(ampacity size, drop size)

    2.5 mm²

Worked example

  • 10 kW three-phase inverter, 415 V, 25 m copper run, 1% target.
  • I_ac = 10 000 / (1.732 × 415 × 1) = 13.9 A; device = 20 A.
  • A_min = 1.732 × 0.0172 × 25 × 13.9 / (0.01 × 415) = 2.5 mm² → 4 mm² after derating check.

Assumptions

  • Unity power factor grid-tied inverter and balanced three-phase output.

Tips

  • Where the run exceeds 40 m, go one size up: the cost is small against lost generation.

Warnings

  • Grid over-voltage tripping is very often caused by an undersized inverter AC cable — never exceed 1%.
  • The AC isolator and RCD must be rated for the selected device current.

Standards & references

  • IEC 62109
  • IEC 60364-7-712
  • IS 732:2019

Frequently asked questions

What cable size does a 10 kW inverter need?

About 13.9 A at 415 V three phase, so 4 mm² copper is typical for runs up to about 30 m with a 1% voltage-drop target.

Why keep the AC voltage drop to 1%?

Grid inverters shut down when the terminal voltage exceeds the statutory limit. A high cable drop pushes the inverter terminal voltage up during export and causes nuisance tripping.

Do I size on inverter rating or panel capacity?

On the inverter's maximum continuous AC output, because that is the highest current the cable will ever carry.

Related calculators