How do I convert kW to kVA?+
Divide the real power by the power factor: kVA = kW / cos φ. At 0.85 pf, 250 kW needs 294 kVA.
What loading should a transformer run at?+
Design for 70–80% of nameplate rating at peak. That leaves headroom for growth and keeps insulation temperature within design life.
What does 5% impedance mean?+
It is the primary voltage, as a percentage of rated voltage, needed to circulate full-load current with the secondary shorted. It sets the short-circuit current — roughly 20 × full load at 5%.
What inputs does the Transformer Sizing Calculator use?+
It uses Connected load, Average power factor, Diversity factor, Future spare capacity, Primary voltage, Secondary voltage, and Impedance. Follow the unit printed for each field and choose any selectable option to match the real scenario.
What does the Transformer Sizing Calculator calculate?+
It calculates Standard rating to select, Required capacity, Loading at peak, HV full-load current, LV full-load current, LV short-circuit current, and Spare capacity. With the displayed default inputs, Standard rating to select is 315 kVA.
Which formula does the Transformer Sizing Calculator use?+
The primary relationship is kVA = kW × diversity / cos φ × (1 + spare). The page also shows substituted values and calculation steps so the result can be checked independently.
How can I verify a Transformer Sizing Calculator result?+
First verify the units for Connected load, Average power factor, and Diversity factor. Then compare the substituted formula steps with Standard rating to select and its displayed precision.
What are the limitations of the Transformer Sizing Calculator?+
Transformer Sizing Calculator: Use this result for preliminary design and cross-checking. Confirm the applicable code edition, manufacturer data, site conditions and qualified-engineer approval before final design or installation.