What is the maximum voltage drop allowed by the NEC?+
The NEC does not enforce a limit, but informational notes to 210.19(A) and 215.2(A) recommend a maximum of 3% on a branch circuit and 5% for the feeder and branch circuit combined. This calculator checks against whichever target you select.
What size wire do I need for a 100 ft run at 30 amps?+
At 240 V single phase, 10 AWG copper gives about 3.0% drop — right at the limit — so most electricians use 8 AWG, which comes in near 1.9%. At 120 V the same 30 A load over 100 ft needs 6 AWG to stay under 3%.
How do I calculate voltage drop in AWG wire?+
Vd = 2 × I × R for single-phase or DC, and √3 × I × R for three-phase, where R is the NEC Chapter 9 Table 8 resistance in ohms per 1000 ft multiplied by the one-way run in feet divided by 1000. This tool does it, plus the ampacity check.
Does the NEC allow the 90 °C column for sizing?+
Only for applying ambient and bundling correction factors. Under 110.14(C) the final ampacity is limited to the 60 °C column for circuits at 100 A or less, and the 75 °C column above that, unless every termination is rated 90 °C.
What is an acceptable voltage drop under IEC rules?+
3% for lighting circuits and 5% for power circuits measured from the origin of the installation is the widely accepted limit in IEC-based codes such as IEC 60364 and IS 732.
Does voltage drop waste energy?+
Yes. The dropped voltage times the current is dissipated as heat in the wire — this calculator reports that loss in watts and kWh per year.
What inputs does the Voltage Drop Calculator use?+
It uses Code / units, System, Current, System voltage, One-way length, Conductor cross-section, Conductor material, Conductor operating temperature, Permitted drop, and Parallel runs. Follow the unit printed for each field and choose any selectable option to match the real scenario.
What does the Voltage Drop Calculator calculate?+
It calculates Voltage drop, Status, Voltage at the load, Conductor resistance, Power loss in cable, and Minimum size for the limit. With the displayed default inputs, Voltage drop is 5.7 V.