ACSR conductor · 400 mm² nominal

DEER Conductor — Specification & Current Carrying Capacity

30/4.27 mm Al + 7/4.27 mm steel · 529.80 mm² total area · 29.89 mm overall diameter · 1975 kg/km · 0.0674 Ω/km at 20 °C · 175.60 kN breaking load · about 700 A.

220 kV transmission lines where a high-strength conductor is required.

Full technical specification

Data basis: IS 398 and standard manufacturer catalogues. Individual manufacturers vary slightly — confirm against the supplier datasheet before final design.

Code nameDEER
FamilyACSR
MaterialAluminium strands over a 7-wire galvanised steel core
Stranding30/4.27 mm Al + 7/4.27 mm steel
Aluminium strands30 × 4.27 mm
Steel strands7 × 4.27 mm
Aluminium area429.60 mm²
Steel area100.20 mm²
Total area529.80 mm²
Nominal (trade) area400 mm²
Overall diameter29.89 mm
Approximate weight1975 kg/km
DC resistance at 20 °C0.0674 Ω/km
Calculated AC resistance at 75 °C0.0865 Ω/km
Ultimate breaking load175.60 kN
Current carrying capacity700 A (standard basis)

Construction of DEER

DEER is built as 30/4.27 mm Al + 7/4.27 mm steel. Aluminium strands over a 7-wire galvanised steel core. The steel core takes most of the mechanical tension so the aluminium can be sized purely for current, which is what lets ACSR span long distances between towers. The total metallic area of 529.80 mm² and overall diameter of 29.89 mm set both the resistance and the wind/ice loading the structures must carry.

Where DEER is used

220 kV transmission lines where a high-strength conductor is required. At 700 A on the standard basis, a three-phase circuit of DEER carries roughly 13 MVA at 11 kV, 40 MVA at 33 kV and 160 MVA at 132 kV — useful as a first sanity check before detailed load flow.

Conditions behind the current rating

Ambient 40 °C, maximum conductor temperature 75 °C, cross-wind 0.61 m/s, solar radiation 1000 W/m², emissivity 0.9, absorptivity 0.8, outdoor overhead installation (IEEE 738 / IS 398 practice).

  • Wind is the single biggest variable. Removing it drops the rating of DEER from 759 A to 434 A in the cases above.
  • Raising the permitted conductor temperature increases the rating, but sag and long-term annealing of the aluminium set the practical ceiling — 75 °C continuous is the usual limit.
  • A weathered, dark conductor absorbs more sunlight but also radiates heat better; the standard 0.8 absorptivity / 0.9 emissivity pair is the conservative combination.
  • Terminations, jumpers and clamps often limit a line before the conductor does. Check the whole current path, not only the span.