AAC conductor · 60 mm² nominal

WASP Conductor — Specification & Current Carrying Capacity

7/3.40 mm Al · 63.55 mm² total area · 10.20 mm overall diameter · 174 kg/km · 0.4626 Ω/km at 20 °C · 10.20 kN breaking load · about 225 A.

LT mains and short 11 kV spans in polluted or coastal environments.

Full technical specification

Data basis: IS 398 and standard manufacturer catalogues. Individual manufacturers vary slightly — confirm against the supplier datasheet before final design.

Code nameWASP
FamilyAAC
MaterialAll-aluminium stranded conductor (no steel core)
Stranding7/3.40 mm Al
Aluminium strands7 × 3.4 mm
Steel strandsNone
Aluminium area63.55 mm²
Steel area
Total area63.55 mm²
Nominal (trade) area60 mm²
Overall diameter10.20 mm
Approximate weight174 kg/km
DC resistance at 20 °C0.4626 Ω/km
Calculated AC resistance at 75 °C0.5934 Ω/km
Ultimate breaking load10.20 kN
Current carrying capacity225 A (standard basis)

Construction of WASP

WASP is built as 7/3.40 mm Al. All-aluminium stranded conductor (no steel core). With no steel core the whole cross-section conducts, giving the lowest resistance per mm² of any of the families, at the cost of breaking load. The total metallic area of 63.55 mm² and overall diameter of 10.20 mm set both the resistance and the wind/ice loading the structures must carry.

Where WASP is used

LT mains and short 11 kV spans in polluted or coastal environments. At 225 A on the standard basis, a three-phase circuit of WASP carries roughly 4 MVA at 11 kV, 13 MVA at 33 kV and 51 MVA at 132 kV — useful as a first sanity check before detailed load flow.

Conditions behind the current rating

Ambient 40 °C, maximum conductor temperature 75 °C, cross-wind 0.61 m/s, solar radiation 1000 W/m², emissivity 0.9, absorptivity 0.8, outdoor overhead installation (IEEE 738 / IS 398 practice).

  • Wind is the single biggest variable. Removing it drops the rating of WASP from 220 A to 113 A in the cases above.
  • Raising the permitted conductor temperature increases the rating, but sag and long-term annealing of the aluminium set the practical ceiling — 75 °C continuous is the usual limit.
  • A weathered, dark conductor absorbs more sunlight but also radiates heat better; the standard 0.8 absorptivity / 0.9 emissivity pair is the conservative combination.
  • Terminations, jumpers and clamps often limit a line before the conductor does. Check the whole current path, not only the span.