Explicit checks passed
3 explicit checks passed for the entered values. This does not replace independent verification where the decision is safety-critical, contractual, statutory, financial or medical.
Measured plant PR and specific yield per IEC 61724-1.
PerformanceSigned — can be below 0 °C in cold climates.
Signed, typically negative — never enter as a positive number.
Solar PV decision support
This section organises the existing calculator output into design checks, governing criteria and comparison cases. Core solar formulas and the calculator's original results are unchanged.
Explicit checks passed
3 explicit checks passed for the entered values. This does not replace independent verification where the decision is safety-critical, contractual, statutory, financial or medical.
Governing criterion
Measured AC yield ÷ reference irradiation yield
83.3 %
PR compares measured AC specific yield with the plane-of-array reference yield over the same measurement interval.
Solar engineering check 1
pass✓ PASS — PR is below the 90% level typically associated with metering error.
Structured directly from this solar calculator's own runtime alert.
Solar engineering check 2
pass✓ PASS — Measurement period ≥ 30 days gives a reasonably representative PR.
Structured directly from this solar calculator's own runtime alert.
Solar engineering check 3
pass✓ PASS — Ground-based irradiance sensor used — good data quality basis.
Structured directly from this solar calculator's own runtime alert.
Measured PR review
info83.3%
Use consistent AC energy and plane-of-array irradiation measurement intervals when trending PR.
Engine recommendation 1
POA-based PR is the IEC 61724-1-correct basis for this result.
Engine recommendation 2
Report PR alongside the measurement period and sensor type for auditability.
Engine recommendation 3
Engineering-grade preliminary calculation. Final design must be verified against project-specific site conditions, manufacturer datasheets, applicable standards and utility requirements.
Primary design output
83.3 %
Excellent
Measurement-quality check
Use synchronized AC energy and calibrated POA irradiation data
PR is only meaningful when energy and irradiation cover the same interval and the sensor/meter chain is reliable.
Lower and higher cases are recalculated by the same solar calculator engine. They are comparison cases, not weather forecasts or guaranteed production values.
Lower measured AC energy
measured AC energy = 1000
Current inputs
measured AC energy = 1250
Higher measured AC energy
measured AC energy = 1500
Decision sensitivity
measured AC energy · up
For the same calculator engine, the lower case changes Performance ratio by -19.9% and the higher case by +20.0%.
This is a deterministic input sensitivity check, not a statistical uncertainty or weather forecast.
Methodology & limit
Decision support is structured from the existing solar calculator engine and the current user inputs. PASS/FAIL is shown only where the engine or entered project criteria support an explicit check. Final PV design still requires site survey, exact module/inverter datasheets, structural/electrical design and applicable statutory approval.
Interpretation band: Excellent.
Designs are stored privately in this browser — nothing is uploaded.
PR compares the plant's actual specific yield with the yield it would deliver at STC efficiency under the measured irradiation. It isolates losses (soiling, thermal, wiring, inverter, downtime) from weather variation, so PR is comparable across sites and seasons. Temperature correction removes the thermal component so that only controllable losses remain.
E_AC/P_DC125 kWh/kWpH/1kW/m²150 hYf/Yr83.33 %1+γ(Tcell−25)0.93PR/[1+γ(Tcell−25)]89.61 %Measured plant PR and specific yield per IEC 61724-1. The example below is calculated by this page's real engine from the displayed inputs.
Use values from the same measurement basis and time period. Conditional fields appear only when the related option is selected.
| Input | Example value | Why it matters |
|---|---|---|
| Installed DC capacity | 10 kWp | Measured or known installed dc capacity used by the calculation engine. |
| Plane-of-array irradiation | 150 kWh/m² | Measured or known plane-of-array irradiation used by the calculation engine. |
| Irradiation measurement type | POA (plane-of-array) — correct basis | Select the option that matches the real installation or scenario. |
| Measured AC energy | 1250 kWh | Measured or known measured ac energy used by the calculation engine. |
| Average cell temperature | 45 °C | Signed — can be below 0 °C in cold climates. |
| Power temperature coefficient γ | -0.35 %/°C | Signed, typically negative — never enter as a positive number. |
| Measurement period | 30 days | Measured or known measurement period used by the calculation engine. |
| Irradiance sensor type | Calibrated pyranometer | Select the option that matches the real installation or scenario. |
These are the named quantities used by this calculator. When the source formula does not define a mathematical symbol, OneCalcApp keeps the real input label instead of inventing one.
| Variable / input | Unit | Meaning in this calculation |
|---|---|---|
| Installed DC capacity | kWp | Measured or known installed dc capacity used by the calculation engine. |
| Plane-of-array irradiation | kWh/m² | Measured or known plane-of-array irradiation used by the calculation engine. |
| Irradiation measurement type | — | Select the option that matches the real installation or scenario. |
| Measured AC energy | kWh | Measured or known measured ac energy used by the calculation engine. |
| Average cell temperature | °C | Signed — can be below 0 °C in cold climates. |
| Power temperature coefficient γ | %/°C | Signed, typically negative — never enter as a positive number. |
| Measurement period | days | Measured or known measurement period used by the calculation engine. |
| Irradiance sensor type | — | Select the option that matches the real installation or scenario. |
The Performance Ratio (PR) uses Installed DC capacity, Plane-of-array irradiation, Irradiation measurement type, Measured AC energy, Average cell temperature, Power temperature coefficient γ, Measurement period, and Irradiance sensor type to calculate Performance ratio, Temperature-corrected PR, Final (specific) yield Yf, Reference yield Yr, and Irradiation basis. Its engine applies Yf = E_AC / P_DC (final/specific yield, kWh/kWp); the worked values below come from that same live calculation rather than a separately typed example.
With Installed DC capacity 10 kWp, Plane-of-array irradiation 150 kWh/m², Irradiation measurement type POA (plane-of-array) — correct basis, Measured AC energy 1250 kWh, Average cell temperature 45 °C, Power temperature coefficient γ -0.35 %/°C, Measurement period 30 days, and Irradiance sensor type Calibrated pyranometer, the main worked-example result is Performance ratio = 83.3 %.
The Performance Ratio (PR) worked example uses Installed DC capacity = 10 kWp. This value is passed directly into the calculation, with an allowed minimum 0.1.
The Performance Ratio (PR) worked example uses Plane-of-array irradiation = 150 kWh/m². This value is passed directly into the calculation, with an allowed minimum 0.1.
The Performance Ratio (PR) worked example selects “POA (plane-of-array) — correct basis”. Available choices include POA (plane-of-array) — correct basis and GHI (global horizontal) — limitation applies. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
The Performance Ratio (PR) worked example uses Measured AC energy = 1250 kWh. This value is passed directly into the calculation, with an allowed minimum 0.1.
The Performance Ratio (PR) worked example uses Average cell temperature = 45 °C. This value is passed directly into the calculation, with an allowed minimum -20 and maximum 90. Signed — can be below 0 °C in cold climates.
The Performance Ratio (PR) worked example uses Power temperature coefficient γ = -0.35 %/°C. This value is passed directly into the calculation, with an allowed minimum -0.6 and maximum 0. Signed, typically negative — never enter as a positive number.
The Performance Ratio (PR) worked example uses Measurement period = 30 days. This value is passed directly into the calculation, with an allowed minimum 1 and maximum 366.
The Performance Ratio (PR) worked example selects “Calibrated pyranometer”. Available choices include Calibrated pyranometer, Reference cell, and Satellite-derived. This selection may change the method or factor used by the engine, so choose the option that matches the real case.
In the Performance Ratio (PR), Yf = E_AC / P_DC (final/specific yield, kWh/kWp). The quantities in this relationship come from the named inputs or from an earlier calculation step shown in the worked example.
In the Performance Ratio (PR), Yr = H_POA / 1 kW/m² (reference yield, h). The quantities in this relationship come from the named inputs or from an earlier calculation step shown in the worked example.
In the Performance Ratio (PR), PR = Yf / Yr. The quantities in this relationship come from the named inputs or from an earlier calculation step shown in the worked example.
In the Performance Ratio (PR), PR_temp-corrected (IEC 61724-1) = PR / [1 + γ(Tcell − 25)] (γ signed). The quantities in this relationship come from the named inputs or from an earlier calculation step shown in the worked example.
For the displayed Performance Ratio (PR) worked example, Performance ratio is 83.3 %. Excellent Verify Installed DC capacity, Plane-of-array irradiation, and Irradiation measurement type and their units before relying on this output.
For the displayed Performance Ratio (PR) worked example, Temperature-corrected PR is 89.6 %. Verify Installed DC capacity, Plane-of-array irradiation, and Irradiation measurement type and their units before relying on this output.
For the displayed Performance Ratio (PR) worked example, Final (specific) yield Yf is 125 kWh/kWp. Verify Installed DC capacity, Plane-of-array irradiation, and Irradiation measurement type and their units before relying on this output.
For the displayed Performance Ratio (PR) worked example, Reference yield Yr is 150 h. Verify Installed DC capacity, Plane-of-array irradiation, and Irradiation measurement type and their units before relying on this output.
For the displayed Performance Ratio (PR) worked example, Irradiation basis is POA — correct basis. Verify Installed DC capacity, Plane-of-array irradiation, and Irradiation measurement type and their units before relying on this output.
Read the main result together with supporting checks, assumptions, limits and intermediate values.
For a manual check, repeat the first equation, confirm the units and change one input at a time.
Performance Ratio (PR) is designed for cases where Installed DC capacity, Plane-of-array irradiation, Irradiation measurement type, Measured AC energy are known and you need Performance ratio, Temperature-corrected PR, Final (specific) yield Yf. The page keeps the live calculator, calculation method and worked example together so the result can be checked instead of treated as a black-box number.
Use the calculator for the scope described by its inputs and notes. The displayed method is Yf = E_AC / P_DC (final/specific yield, kWh/kWp). If the real project or decision needs factors that are not represented here, treat the result as an estimate and add the missing checks separately.
The worked example uses Installed DC capacity = 10 kWp, Plane-of-array irradiation = 150 kWh/m², Irradiation measurement type = POA (plane-of-array) — correct basis, Measured AC energy = 1250 kWh. With those values, Performance ratio is 83.3 %. Changing an input should be interpreted according to that field's unit, range, option and hint rather than by the number alone.
For this calculator, the main input roles are: Installed DC capacity (kWp): Measured or known installed dc capacity used by the calculation engine. Plane-of-array irradiation (kWh/m²): Measured or known plane-of-array irradiation used by the calculation engine. Irradiation measurement type: Select the option that matches the real installation or scenario. Available choices include POA (plane-of-array) — correct basis, GHI (global horizontal) — limitation applies. Measured AC energy (kWh): Measured or known measured ac energy used by the calculation engine.
Start by confirming the entered values and units, then compare the substituted working with the displayed formula or calculation steps. Pay particular attention to Performance ratio, because it is the first worked-example output shown by the live engine.
Finally, compare the result with the assumptions, warnings and related calculators on this page. A nearby calculator can be useful as a cross-check when it measures the same workflow from a different input or output direction.
Next logical calculator
Solar Generation Calculator covers the same practical workflow from a related calculation angle, making it a useful cross-check after Performance Ratio (PR).
Open Solar Generation CalculatorReferences show the method used. Check the current local edition, amendments and project specification before a regulated decision.
Azimuth Deviation Loss
Annual energy loss vs deviation from true south (N-hem).
Shading Loss
Annual generation loss from partial shading.
Temperature Loss
Power derating from cell temperature above STC 25 °C.
Irradiance → Energy
PV energy produced from measured irradiance.
Peak Sun Hours
Convert daily insolation to Peak Sun Hours.
Monthly Yield Split
Distribute annual generation across months (India typical).
Deeper reading on the engineering behind this calculation.
PV System Size Calculator: How to Calculate the Right Solar PV System Size
The full PV sizing chain — load, peak sun hours, performance ratio, required DC capacity, module count, inverter capacity and DC/AC ratio — with worked equations.
Read Article →How Many Solar Panels Do I Need? Complete PV Module Sizing Guide
Turn your electricity bill into a panel count: load, required DC capacity, module wattage, inverter sizing, plus illustrative examples from 3 kW to 1 MW.
Read Article →Solar PV Performance Ratio (PR): Complete Guide to PV System Losses
What performance ratio means, every loss term from temperature to availability, how the losses multiply, and how PR differs from efficiency and capacity factor.
Read Article →How to Size a Solar PV System Correctly
A step-by-step engineering walkthrough covering load assessment, peak sun hours, performance ratio and module selection.
Read Article →